Field Pocket Guide

Thermocouple Tables

Eight letter types, ITS-90, reference junction at 0 °C. Convert temperature to millivolts and back with cold-junction compensation, or generate a reference table at any interval. Built straight from the NIST reference functions.

Guided setup

Tell me the type, the direction, your reading, and the cold-junction reference. The wizard runs the exact same ITS-90 math as the form, and it will confirm the reference since 0 °C versus ambient changes the answer.

The wizard only asks questions and runs the calculator. Every number comes from the deterministic engine, not the AI.

Thermocouple type

Convert


Meter reads
—mV
E(hot), ref 0 °C
—mV
E(cold junction)
—mV

Reference table · absolute, ref 0 °C

°CmV°CmV
00.00051021.071
100.39752021.497
200.79853021.924
301.20354022.350
401.61255022.776
502.02356023.203
602.43657023.629
702.85158024.055
803.26759024.480
903.68260024.905
1004.09661025.330
1104.50962025.755
1204.92063026.179
1305.32864026.602
1405.73565027.025
1506.13866027.447
1606.54067027.869
1706.94168028.289
1807.34069028.710
1907.73970029.129
2008.13871029.548
2108.53972029.965
2208.94073030.382
2309.34374030.798
2409.74775031.213
25010.15376031.628
26010.56177032.041
27010.97178032.453
28011.38279032.865
29011.79580033.275
30012.20981033.685
31012.62482034.093
32013.04083034.501
33013.45784034.908
34013.87485035.313
35014.29386035.718
36014.71387036.121
37015.13388036.524
38015.55489036.925
39015.97590037.326
40016.39791037.725
41016.82092038.124
42017.24393038.522
43017.66794038.918
44018.09195039.314
45018.51696039.708
46018.94197040.101
47019.36698040.494
48019.79299040.885
49020.218100041.276
50020.644

Cold-junction compensation. The tables are absolute, referenced to 0 °C. A real meter sees only the difference between the hot junction and its own terminals, so the millivolts at the meter equal E(hot) − E(cold junction). Set the reference to your terminal block temperature and the converter does it for you.

Still not reading right?

If the numbers here do not match what the loop is doing, the problem is usually the installation, the ranging, or the process itself rather than the device. Describe the symptom and a specialist answers by email, at no charge.